General Applications study guide
- Questions on the exam
- 8–12
- Practice questions published
- 11
Watch the lesson
What this area covers
General Applications spans more separate topics than any other area and feels most like day-to-day facility and utility work. It gathers load characteristics (demand, diversity and load factor), interior lighting design, grounding, surge protection, power factor at the service, and the engineering economics that decides whether an improvement is worth paying for. This area accounts for 8–12 questions on the exam. The individual topics are not deep, but there are many of them, so breadth beats depth here.
The ideas everything else rests on
Load is described by ratios. Demand factor compares the maximum demand of a group of loads with its total connected load, and is at most one. Diversity factor compares the sum of individual peak demands with the peak of the group, and is at least one, because loads rarely peak together. Load factor compares average demand with peak demand over a period. Each ratio answers a different sizing question, so read carefully which one is given.
The lumen method is a light budget. The light a room needs, illuminance times area, must be delivered by luminaires after losses. The number of luminaires is
where the coefficient of utilisation accounts for room shape and surface reflectances, and the light loss factor accounts for lamp depreciation and dirt over time.
Grounding is about resistance to remote earth and about bonding. A single driven rod's resistance depends mostly on soil resistivity and rod length, and only weakly on diameter. Adding rods helps only if they are spaced far enough apart that their zones of influence do not overlap much. Measuring that resistance with the fall-of-potential method needs the potential probe placed outside both electrodes' zones of influence.
A surge arrester must survive normal voltage and still protect. Its maximum continuous operating voltage (MCOV) must be at least the highest continuous line-to-ground voltage at its location. On an effectively grounded system, the short rise on unfaulted phases during a ground fault is checked separately, against the arrester's temporary overvoltage (TOV) capability for the time the fault lasts. On ungrounded or high-impedance grounded systems, where a ground fault can stay on, the MCOV must reach line-to-line voltage. Its protective level must sit far enough below the equipment's insulation withstand to leave a healthy protective margin.
Money has a time value. Comparing alternatives means bringing every cost to one point in time. A single future amount converts to present worth as
and series of equal annual amounts use the matching uniform-series factors. The alternative with the lowest present worth of cost, or the highest net present worth, wins.
How to study it
- Work demand, diversity and load factor from a small table of loads you invent, and use the results to size a feeder or a service transformer.
- Check service-level power with the Three-phase power calculator, then size a capacitor bank to remove a power-factor penalty with the Power-factor correction calculator.
- Lay out a rectangular room with the lumen method: compute the room cavity ratio, look up a coefficient of utilisation from a manufacturer-style table you build yourself, and count luminaires.
- Study grounding electrodes and the fall-of-potential test, then work arrester selection: the MCOV for solidly grounded and for ungrounded systems, and the protective margin against a given insulation level.
- Close with economics: present worth, annual worth and simple payback for a loss-reduction project, and check feeder losses or drop with the Voltage drop calculator.
Mistakes that cost points
- Swapping demand and diversity factor. One is at most one, the other at least one. If your answer lands on the wrong side of one, you divided the wrong way.
- Using the initial lumen rating with no light loss factor. The design should meet the target after depreciation, not on the first day.
- Choosing MCOV from line-to-ground voltage on an ungrounded system. A ground fault can stay on such a system, holding the healthy phases near line-to-line voltage, so the MCOV must cover that. On an effectively grounded system, check the fault-time rise against TOV capability instead.
- Mixing nominal and effective interest rates. Match the rate to the compounding period before using any factor.
References worth having
- IEEE Std 141 (Red Book): the load and power factor chapters
- IEEE Std 142 (Green Book): the grounding electrode chapter
- IEEE Std C62.22 (application of metal-oxide surge arresters)
- IES Lighting Handbook
Try a free question
- Demand and load factor billMultiple choiceWarm-up
- Point-by-point illuminanceMultiple choiceWarm-up
- Lumen method luminaire countMultiple choiceWarm-up
- Ground rod resistanceMultiple choiceExam level
Calculators for this area
Power-factor correction calculator
Capacitor kVAR and µF per phase to raise a lagging power factor, and the line current before and after.
Open the calculatorThree-phase power calculator
kW, kVA, kVAR, line current and power factor from the line voltage and any two of them.
Open the calculatorVoltage drop calculator
Feeder voltage drop from current, length, conductor R and X, and power factor.
Open the calculator
Practice every General Applications question
The full set comes with worked solutions and video solutions you can open after you answer. Start with the free diagnostic to see where you stand.
Lesson transcript
The narration of “General Applications in 4 minutes”, by chapter.
Introduction
General applications in four minutes. This area spans more separate topics than any other, and it feels most like day-to-day facility and utility work. We will cover load ratios, lighting, grounding, surge arresters, and engineering economics. Then work one lighting example and look at two traps.
What to expect
Expect eight to twelve questions from this area. No single topic goes very deep, but there are many of them, so breadth beats depth. You should be able to describe a load with its ratios, lay out the lights in a room, reason about ground rods, select a surge arrester, and compare the cost of two alternatives.
Load ratios
Idea one, load is described by ratios. Demand factor compares the peak demand of a group with its connected load, so it is at most one. Diversity factor compares the sum of the individual peaks with the peak of the group. Loads rarely peak together, so it is at least one. Load factor compares average demand with peak demand over a period.
Lighting
Idea two, the lumen method is a light budget. The room needs its target illuminance times its area in lumens. Each luminaire delivers its rated lumens times a coefficient of utilization for the room's shape and surfaces times a light loss factor for lamp aging and dirt. Divide the first by the second to count luminaires.
Grounding
Idea three, grounding is about resistance to remote earth. A single rod's resistance depends mostly on the soil and the rod length and only weakly on its diameter. Extra rods help only when they are spaced far enough apart that their zones of influence barely overlap. Testing by fall of potential needs the probe outside both zones.
Surge arresters
Idea four, a surge arrester must survive normal voltage and still protect. Its continuous rating must be at least the highest continuous line-to-ground voltage where it sits. On an ungrounded system, a ground fault can stay on, so that rating must reach line-to-line voltage. Its protective level must sit well below the insulation withstand of the equipment, leaving a healthy margin.
Economics
Idea five, money has a time value. To compare alternatives bring every cost to one point in time. A future amount becomes a present worth when you divide it by one plus the interest rate raised to the number of periods. The alternative with the lowest present worth of cost wins.
Mini-example
Now a mini-example. A room is 40 feet by 30 feet and it needs 50 foot-candles. Each luminaire is rated 5,000 lumens with a coefficient of utilization of 0.6 and a light loss factor of 0.8. How many luminaires do you need? The area is 1,200 square feet so the room needs 50 times 1,200 or 60,000 lumens. Each luminaire delivers 5,000 times 0.6 times 0.8 which is 2,400 lumens. 60,000 over 2,400 gives 25 luminaires. Round up whenever the division does not come out whole.
Two traps
Trap one, leaving out the light loss factor. Divide 60,000 by 3,000 lumens and you get 20 luminaires which meets the target only on the first day. The design has to hold after the lamps age and the room gets dirty. Trap two, swapping demand and diversity factor. Three loads peak at 40, 30, and 50 kilowatts, a sum of 120, but together they peak at 80. The diversity factor is 120 over 80 or 1.5. Divide the other way and you get 0.67 which is below 1 so you know you flipped it. Find out where you stand with the free diagnostic then practice this area with worked solutions at phasorprep.com