Voltage drop calculator
Feeder voltage drop from current, length, conductor R and X, and power factor.
Result
- Voltage drop
- 3.674V
- Of nominal
- 0.919%
- R over the length
- 0.02Ω
- X over the length
- 0.008Ω
The formula
The drop along a feeder is the component of the I·Z drop that lies along the receiving-end voltage, where Z is the conductor impedance. With R and X per unit length of one conductor and L the one-way length:
The single-phase formula counts the conductor out and the conductor back, hence the 2. The three-phase formula gives the line-to-line drop of a balanced load, hence the square root of 3. Both leave out the small component of the drop at right angles to the voltage, which is why they are called approximate; for drops of a few percent the error is negligible.
Getting R
Use the resistance from the cable manufacturer or from the impedance table of the code edition you design to. If you only know the conductor size, the helper estimates DC resistance from the resistivity at 20 °C, corrected to the operating temperature:
It uses 0.017241 Ω·mm²/m and 0.00393 per °C for copper, 0.028264 Ω·mm²/m and 0.00403 per °C for aluminum, and 1 kcmil = 0.506707 mm².
Worked example
A balanced three-phase load draws 100 A at 0.85 power factor, lagging, from a 400 V source through 100 m of cable with R = 0.2 Ω/km and X = 0.08 Ω/km. The length is 0.1 km, cos φ = 0.85 and sin φ = 0.5268:
Switch the power factor to leading and the reactive term changes sign: the drop falls to 2.215 V. The result turns negative, a voltage rise toward the load, only when the load leads and X sin φ is larger than R cos φ: a strongly leading load on a cable whose reactance is large next to its resistance.
Questions
Is this the exact voltage drop?
Why does power factor change the voltage drop?
Where do the R and X values come from?
For learning, not for design
Practice questions are on the way
Original PE Power questions, each with a verified worked solution. Join the waitlist to hear when the free diagnostic opens.