Power-factor correction calculator
Capacitor kVAR and µF per phase to raise a lagging power factor, and the line current before and after.
Result
- Capacitor bank
- 276.6kVAR
- Per phase, delta bank
- 1,062µF
- Per phase, wye bank
- 3,185µF
- Apparent power, before
- 666.7kVA
- Apparent power, after
- 526.3kVA
- Line current, before
- 801.9A
- Line current, after
- 633.1A
What it calculates
The capacitor bank that raises a lagging power factor to a target. The real power stays the same; the bank supplies part of the reactive power, so the apparent power and the line current fall. The reactive power the bank must supply is the difference between the two reactive loads, found from the tangent of each power-factor angle:
Dividing that reactive power among the three phases and applying the capacitor equation gives the capacitance to install in each phase, which depends on how the bank is connected:
Delta or wye bank
A delta-connected capacitor sees the full line-to-line voltage. A wye-connected capacitor sees only the line-to-neutral voltage, which is lower by a factor of √3. Reactive power goes with voltage squared, so a wye capacitor must be three times larger to supply the same kVAR. Both results are shown; use the one that matches how the bank is wired.
Worked example
A 480 V plant draws 500 kW at a power factor of 0.75 lagging, and the goal is 0.95. The bank size and the capacitance per phase of a delta bank at 60 Hz are:
A wye bank would need 3,185 µF per phase. Apparent power falls from 666.7 kVA to 526.3 kVA, and the line current from 801.9 A to 633.1 A, which is the saving that lets the same feeder and transformer carry more load.
Assumptions
- The load is lagging, and the target power factor is higher than the present one and at most 1.
- The load is balanced, and power factor is the displacement power factor at the fundamental frequency. Harmonics are not included.
- The capacitors are rated at the system voltage. A capacitor run at a different voltage supplies kVAR in proportion to the square of that voltage.
Questions
Why are the wye microfarads three times the delta microfarads?
Why not correct all the way to unity power factor?
Does this account for harmonics?
Study areas that use this
For learning, not for design
Practice questions are on the way
Original PE Power questions, each with a verified worked solution. Join the waitlist to hear when the free diagnostic opens.
See the Founding Pass