Transmission and Distribution study guide
- Questions on the exam
- 8–12
- Practice questions published
- 11
Watch the lesson
What this area covers
Transmission and Distribution is about moving power from where it is made to where it is used while keeping voltage in range and the system in step. It covers line models, voltage drop and regulation, how real and reactive power flow, reactive compensation, fault current on networks, and the basics of transient stability. This area accounts for 8–12 questions on the exam. The work is mostly calculation, and it goes faster with a clean per-phase diagram drawn before any numbers go in.
The ideas everything else rests on
Pick the line model by length. A short line is a series impedance and nothing else. A medium line adds shunt capacitance, usually split half at each end in a nominal pi. A long line needs distributed parameters and hyperbolic functions. The model you pick decides whether receiving-end voltage can rise above sending-end voltage at light load, the Ferranti effect, which only appears once shunt capacitance is in the model.
Voltage drop follows the power factor. For a short line, the drop along the line is close to the current times the sum of R times cos θ and X times sin θ. Lagging loads make the reactive term add; leading loads can make the drop negative. Regulation compares no-load and full-load receiving voltage:
Real power follows angle, reactive power follows voltage. Across a mostly inductive line, real power transfer is
so it peaks at 90 degrees and depends on the angle between the ends. Reactive power, by contrast, flows mostly from the higher-voltage end to the lower. This split is why voltage problems are fixed with reactive devices and loading problems with angle or impedance.
Compensation reshapes the line. Shunt capacitors supply reactive power locally and raise voltage under heavy load. Shunt reactors absorb it and hold voltage down at light load. Series capacitors cancel part of the line's reactance, which raises the transfer limit in the equation above.
Stability is a race between energy in and energy out. After a fault, a generator accelerates while its electrical output is depressed. The equal area criterion compares the accelerating area under the power–angle curve with the decelerating area available after clearing. If the second is at least as large as the first, the machine stays in step; the critical clearing angle is where the two are exactly equal.
How to study it
- Solve short-line problems first: sending-end voltage, drop and regulation for lagging, unity and leading loads. Check each with the Voltage drop calculator.
- Move to the nominal pi model. Work ABCD constants for short and medium lines, and compute receiving-end voltage at no load to see the Ferranti rise.
- Put a network on a common base with the Per-unit converter, then find fault current at several buses and confirm with the Fault current calculator. Note how X/R changes from a generator bus to a distribution feeder.
- Size shunt capacitors to raise a bus voltage or improve a feeder's power factor, and check the reactive power with the Power-factor correction calculator.
- Draw power–angle curves for pre-fault, fault-on and post-fault networks, and find the critical clearing angle with the equal area criterion.
Mistakes that cost points
- Using line-to-line voltage in a per-phase drop. Compute drop per phase with line-to-neutral voltage, then convert, or use a formula built for line-to-line values. Never mix the two.
- Losing the sign of sin θ. A leading power factor makes the reactive term negative. Write the angle with its sign before you substitute.
- Doubling the shunt admittance. In a nominal pi, each end gets half of the total. Placing the full value at both ends doubles the charging current.
- Using the wrong curve for each area. The accelerating area uses the fault-on curve; the decelerating area uses the post-fault curve. Swap them and the clearing angle comes out wrong.
References worth having
- Glover, Overbye and Sarma, Power System Analysis and Design: the transmission line and stability chapters
- IEEE Std 141 (Red Book): the voltage considerations chapter
- ANSI C84.1 (service and utilization voltage ranges)
Try a free question
- Substation bus fault currentMultiple choiceWarm-up
- Line-to-ground fault currentMultiple choiceExam level
- Short line voltage regulationMultiple choiceWarm-up
Calculators for this area
Voltage drop calculator
Feeder voltage drop from current, length, conductor R and X, and power factor.
Open the calculatorFault current calculator
Three-phase and line-to-ground fault current at a delta–wye-grounded transformer's secondary.
Open the calculatorPer-unit converter
Base current and impedance, and an impedance moved from one MVA and kV base to another.
Open the calculatorPower-factor correction calculator
Capacitor kVAR and µF per phase to raise a lagging power factor, and the line current before and after.
Open the calculator
Practice every Transmission and Distribution question
The full set comes with worked solutions and video solutions you can open after you answer. Start with the free diagnostic to see where you stand.
Lesson transcript
The narration of “Transmission and Distribution in 4 minutes”, by chapter.
Introduction
Transmission and distribution in four minutes. This area is about moving power from where it is made to where it is used while keeping voltage in range and the system in step. We will cover line models, voltage drop, power transfer, compensation and stability, then work one short example and look at two traps.
What to expect
Expect eight to twelve questions from this area and most of them are calculations. You should be able to pick a line model, find the drop and the regulation, explain how real and reactive power flow, choose a compensation device and reason about stability after a fault.
Line models
Idea one, pick the line model by length. A short line is a series resistance and reactance, nothing else. A medium line adds shunt capacitance, split half at each end in a nominal pi. A long line needs distributed parameters. Only a model with shunt capacitance can show the Ferranti effect where the receiving end rises above the sending end at light load.
Voltage drop
Idea two, voltage drop follows the power factor. Start with the receiving voltage as the reference. The current lags it by the power factor angle. The resistive drop is in phase with the current and the reactive drop leads the current by 90 degrees. Projected onto the reference, the drop is close to the current times R cos theta plus X sin theta.
Power transfer
Idea three, real power follows angle. Reactive power follows voltage. Across a mostly inductive line, real power is the sending voltage times the receiving voltage over X, times the sine of the angle between them. It peaks at 90 degrees and falls to zero at 180. Reactive power flows mostly from the higher voltage end toward the lower.
Compensation
Idea four, compensation reshapes the line. Shunt capacitors supply reactive power locally and hold voltage up under heavy load. Shunt reactors absorb it and hold voltage down at light load. Series capacitors cancel part of the line reactance which raises the transfer limit.
Stability
Idea five, stability is a race between energy in and energy out. During a fault, the generator speeds up because its electrical output drops. The equal area criterion compares the accelerating area under the fault-on curve with the decelerating area under the post-fault curve. If the second is at least as large, the machine stays in step.
Mini-example
Now a mini-example. A short three-phase line feeds a 4 MVA load at 0.8 power factor lagging with 12.47 kV at the receiving end. Each phase has 0.8 ohms of resistance and 1.6 ohms of reactance. Find the voltage drop as a percent of the receiving voltage. The current is 4 MVA over root 3 times 12,470 which is 185.2 amps. R cos theta is 0.64 and X sin theta is 0.96 so together 1.60 ohms. The drop is 185.2 times 1.60 or 296.3 volts per-phase. Divide by the line-to-neutral voltage about 7,200 volts and the drop is 4.12 percent. Notice that most of that drop comes from the reactance not the resistance.
Two traps
Trap one, mixing line-to-line and per-phase values. Divide the same drop by 12,470 volts and you get 2.38 percent which is wrong. A per-phase drop goes with a line-to-neutral voltage. Trap two, losing the sign of sine theta. With a leading power factor the reactive term is negative. In our example the bracket becomes minus 0.32 ohms so the voltage rises by 59.3 volts instead of dropping. Write the angle with its sign before you substitute. Find out where you stand with the free diagnostic then practice this area with worked solutions at phasorprep.com