Fault current calculator: 3-phase and line-to-ground

Three-phase and line-to-ground fault current at a delta–wye-grounded transformer's secondary.

Utility source
MVA
Transformer, delta–wye grounded
MVA
%Z
kV

Result

Three-phase fault
6.973kA
Line-to-ground fault
7.844kA
Base current
836.7A
Total Z1
0.12pu

Z1 = Zs + Zt on a 20 MVA base, with Zs = 0.04 pu and Zt = 0.08 pu.

What it calculates

A bolted fault on the secondary bus of a delta–wye-grounded transformer, fed from a utility source. Everything is worked in per unit on the transformer's own rating, so the transformer impedance is simply its nameplate percent divided by 100, and the source impedance is the ratio of the two MVA values:

Zs=SbaseSscZ_s = \dfrac{S_\text{base}}{S_\text{sc}}Zt=%Z100Z_t = \dfrac{\%Z}{100}

The three-phase fault sees only the positive-sequence impedance:

I3ϕ=IbaseZs+ZtI_{3\phi} = \dfrac{I_\text{base}}{Z_s + Z_t}

A line-to-ground fault puts the positive, negative and zero-sequence networks in series. The delta winding gives zero-sequence current no path back to the source, so the zero-sequence impedance is the transformer's alone:

ISLG=3 Ibase2 (Zs+Zt)+ZtI_\text{SLG} = \dfrac{3\,I_\text{base}}{2\,(Z_s + Z_t) + Z_t}

Assumptions

  • Prefault voltage is 1.0 pu and the fault is bolted, with no arc or ground resistance.
  • Positive and negative-sequence impedances are equal; the zero-sequence impedance is the transformer's.
  • Source and transformer impedances are added as magnitudes, as if they shared one angle.
  • No motor contribution and no DC offset: the result is the symmetrical RMS current.

Worked example

A 20 MVA transformer with 8% impedance and a 13.8 kV secondary is fed from a utility that can deliver 500 MVA of fault power at the primary. First the base current and the source impedance:

Ibase=20 MVA3×13.8 kV=836.7 AI_\text{base} = \dfrac{20\ \text{MVA}}{\sqrt{3} \times 13.8\ \text{kV}} = 836.7\ \text{A}Zs=20500=0.04Z_s = \dfrac{20}{500} = 0.04

Then the two fault currents:

I3ϕ=836.70.04+0.08=6,973 AI_{3\phi} = \dfrac{836.7}{0.04 + 0.08} = 6{,}973\ \text{A}
ISLG=3×836.72 (0.12)+0.08=7,844 AI_\text{SLG} = \dfrac{3 \times 836.7}{2\,(0.12) + 0.08} = 7{,}844\ \text{A}

Here the ground fault is larger than the three-phase fault. The source impedance sits only in the positive- and negative-sequence networks, so it counts at two-thirds weight in the ground fault but at full weight in the three-phase fault. With an infinite source the two currents are equal: tick “infinite source” and both rise to 10.46 kA, the most this transformer can deliver.

The MVA method

The MVA method reaches the three-phase fault current without choosing a base. Each element becomes its own short-circuit MVA, the fault power it could deliver alone with an infinite source behind it: a transformer's is its rating divided by its per-unit impedance, and the utility's is its available fault MVA. Elements in series combine like resistors in parallel, elements in parallel simply add, and the current follows from the final MVA and the bus voltage:

MVAt=MVAratedZt\text{MVA}_\text{t} = \dfrac{\text{MVA}_\text{rated}}{Z_t}1MVAsc=1MVAu+1MVAt\dfrac{1}{\text{MVA}_\text{sc}} = \dfrac{1}{\text{MVA}_\text{u}} + \dfrac{1}{\text{MVA}_\text{t}}I3ϕ=MVAsc3 kVI_{3\phi} = \dfrac{\text{MVA}_\text{sc}}{\sqrt{3}\,\text{kV}}

The same transformer and utility as above:

MVAt=200.08=250\text{MVA}_\text{t} = \dfrac{20}{0.08} = 250MVAsc=500×250500+250=166.7\text{MVA}_\text{sc} = \dfrac{500 \times 250}{500 + 250} = 166.7I3ϕ=166.7 MVA3×13.8 kV=6,973 AI_{3\phi} = \dfrac{166.7\ \text{MVA}}{\sqrt{3} \times 13.8\ \text{kV}} = 6{,}973\ \text{A}

That is the same 6,973 A as the per-unit result, as it must be: the two methods are the same arithmetic in different units. This page uses the MVA method for the three-phase fault only; the line-to-ground fault above needs the sequence networks.

Questions

Why can the ground fault current be larger than the three-phase fault current?
At a delta–wye-grounded transformer the delta winding blocks the source's zero-sequence path, so the zero-sequence impedance is only the transformer's own. Any source impedance makes the positive-sequence impedance larger than the zero-sequence impedance, so the line-to-ground current exceeds the three-phase current. The gap narrows as the source gets stronger, and with an infinite source the two are equal.
What does an infinite source mean?
The utility is treated as having zero impedance, so only the transformer limits the current. It gives the largest fault current that transformer can deliver, and it is a common conservative assumption when the utility's available fault MVA is not known.
Does this include motor contribution or DC offset?
No. It gives the symmetrical RMS current of a bolted fault fed from the utility source alone. Motor contribution, arc resistance and asymmetrical current need a fuller short-circuit study.
What is the MVA method of short-circuit calculation?
Each element becomes its own short-circuit MVA: a transformer's is its MVA rating divided by its per-unit impedance, and the utility's is its available fault MVA. Elements in series combine like resistors in parallel, 1/MVA_sc = 1/MVA_1 + 1/MVA_2, and elements in parallel add. The three-phase fault current is then MVA_sc / (√3 × kV). It gives the same three-phase answer as the per-unit method; the worked example on this page shows both.

Free practice problems that use this

Study areas that use this

For learning, not for design

PhasorPrep is an independent study resource. It is not affiliated with, endorsed by, or sponsored by NCEES. Questions are original and written for practice; they are not actual exam questions. Questions, solutions and videos are written and checked by AI (Claude, by Anthropic); no human engineer or licensed PE reviews each question before it is published. Calculators are for learning, not for engineering design.

Put the methods to work

Original PE Power practice questions, each with a worked solution and an answer recomputed by a script. Find your weak areas with the free diagnostic, or try a sample question first.