Fault current calculator: 3-phase and line-to-ground
Three-phase and line-to-ground fault current at a delta–wye-grounded transformer's secondary.
Result
- Three-phase fault
- 6.973kA
- Line-to-ground fault
- 7.844kA
- Base current
- 836.7A
- Total Z1
- 0.12pu
Z1 = Zs + Zt on a 20 MVA base, with Zs = 0.04 pu and Zt = 0.08 pu.
What it calculates
A bolted fault on the secondary bus of a delta–wye-grounded transformer, fed from a utility source. Everything is worked in per unit on the transformer's own rating, so the transformer impedance is simply its nameplate percent divided by 100, and the source impedance is the ratio of the two MVA values:
The three-phase fault sees only the positive-sequence impedance:
A line-to-ground fault puts the positive, negative and zero-sequence networks in series. The delta winding gives zero-sequence current no path back to the source, so the zero-sequence impedance is the transformer's alone:
Assumptions
- Prefault voltage is 1.0 pu and the fault is bolted, with no arc or ground resistance.
- Positive and negative-sequence impedances are equal; the zero-sequence impedance is the transformer's.
- Source and transformer impedances are added as magnitudes, as if they shared one angle.
- No motor contribution and no DC offset: the result is the symmetrical RMS current.
Worked example
A 20 MVA transformer with 8% impedance and a 13.8 kV secondary is fed from a utility that can deliver 500 MVA of fault power at the primary. First the base current and the source impedance:
Then the two fault currents:
Here the ground fault is larger than the three-phase fault. The source impedance sits only in the positive- and negative-sequence networks, so it counts at two-thirds weight in the ground fault but at full weight in the three-phase fault. With an infinite source the two currents are equal: tick “infinite source” and both rise to 10.46 kA, the most this transformer can deliver.
The MVA method
The MVA method reaches the three-phase fault current without choosing a base. Each element becomes its own short-circuit MVA, the fault power it could deliver alone with an infinite source behind it: a transformer's is its rating divided by its per-unit impedance, and the utility's is its available fault MVA. Elements in series combine like resistors in parallel, elements in parallel simply add, and the current follows from the final MVA and the bus voltage:
The same transformer and utility as above:
That is the same 6,973 A as the per-unit result, as it must be: the two methods are the same arithmetic in different units. This page uses the MVA method for the three-phase fault only; the line-to-ground fault above needs the sequence networks.
Questions
Why can the ground fault current be larger than the three-phase fault current?
What does an infinite source mean?
Does this include motor contribution or DC offset?
What is the MVA method of short-circuit calculation?
Free practice problems that use this
Study areas that use this
For learning, not for design
Put the methods to work
Original PE Power practice questions, each with a worked solution and an answer recomputed by a script. Find your weak areas with the free diagnostic, or try a sample question first.