Circuit Analysis study guide

Questions on the exam
10–15
Practice questions published
14

Watch the lesson

Circuit Analysis in 4 minutes, 4:08, with captions. The toolkit the rest of power engineering borrows from.

Read the lesson transcript

What this area covers

Circuit Analysis is the toolkit the rest of power engineering borrows from. It covers sinusoidal steady state with phasors and complex impedance, balanced and unbalanced three-phase circuits, the per-unit system, symmetrical components, complex power, and a light touch of RL and RC transients. This area accounts for 10–15 questions on the exam, but its reach is wider: protection, transmission, machines and devices all lean on these skills, so time spent here pays off in every other area.

The goal is not to memorise circuits. It is to set up any power circuit quickly, pick a reference, and carry magnitudes and angles through without losing a factor of root three along the way.

The ideas everything else rests on

Phasors turn calculus into algebra. At a single frequency, every voltage and current is a magnitude and an angle, and inductors and capacitors become impedances jX. Kirchhoff's laws still hold, only now with complex numbers. Get fluent switching between rectangular and polar form on your calculator, because every other idea in this area runs on that skill.

A balanced three-phase system reduces to one phase. When sources and loads are balanced, the three phases carry equal currents displaced by 120 degrees, so you can solve one phase and scale up. In a balanced wye, line voltage is root three times phase voltage and leads it by 30 degrees in positive sequence. In a delta, line current is root three times phase current and lags it by 30 degrees. A balanced delta load can always be swapped for an equivalent wye of one third the impedance. Unbalanced systems need all three phases, or symmetrical components.

Per-unit removes the transformers. Choose a common MVA base for the whole system and a voltage base in each zone, set by the transformer ratios. Every impedance then sits on one diagram with no ideal transformers in it. The base impedance in each zone comes from

Zbase=(kVbase)2MVAbaseZ_{base} = \frac{(kV_{base})^2}{MVA_{base}}

and an impedance given on one base moves to another as Z_new = Z_old × (MVA_new / MVA_old) × (kV_old / kV_new)², all in per-unit. A larger MVA base raises the per-unit value; a larger kV base lowers it.

Symmetrical components untangle unbalance. Any set of three unbalanced phasors splits into positive, negative and zero sequence sets. Each set sees its own network, and faults connect those networks in recognisable patterns. The zero-sequence voltage, for example, is

V0=13(Va+Vb+Vc)V_0 = \tfrac{1}{3}(V_a + V_b + V_c)

so it vanishes for any balanced set and measures how much the three phases fail to cancel.

Complex power keeps the bookkeeping honest. S = P + jQ, computed as voltage times the conjugate of current. The power triangle links real power, reactive power and power factor, and it is the starting point for every correction problem.

How to study it

  1. Drill phasor arithmetic until it is automatic: convert, multiply, divide and add in both forms, and check every answer against a quick sketch of the phasor diagram.
  2. Solve balanced three-phase circuits on a per-phase basis, then confirm totals with the Three-phase power calculator. Do wye and delta versions of the same load until the 30-degree shifts feel natural.
  3. Build per-unit impedance diagrams for small systems with one generator, two transformers and a line. Check each change of base with the Per-unit converter and be able to explain where every base came from.
  4. Decompose a few unbalanced sets by hand, then compare against the Symmetrical components calculator. Learn what the three sequence networks look like for a generator, a line and each common transformer connection.
  5. Close with power-triangle work: find the reactive power needed to move a load from one power factor to another, and check with the Power-factor correction calculator.
  6. Finish with a short pass on first-order transients: time constants, initial and final values, and the shape of the exponential between them.

Mistakes that cost points

  • Mixing line and phase quantities. A rating in kV is almost always line-to-line; a per-phase circuit needs line-to-neutral. Write the subscript on every voltage you use.
  • Forgetting the 30-degree shift. Magnitudes can come out right while the angle is wrong, and angle errors carry straight into power factor and sequence answers.
  • Changing base on the wrong side. When a transformer separates two zones, the voltage base changes across it. Converting an impedance with the wrong zone's kV base is a classic, quiet error.
  • Dropping the conjugate. S equals V times the conjugate of I. Without the conjugate, the angle of S comes out wrong; with voltage as the angle reference, the sign of reactive power flips and a lagging load looks leading.

References worth having

  • Glover, Overbye and Sarma, Power System Analysis and Design: the per-unit and symmetrical components chapters
  • Grainger and Stevenson, Power System Analysis
  • IEEE Std 399 (Brown Book): the short-circuit studies chapter

Try a free question

Calculators for this area

Practice every Circuit Analysis question

The full set comes with worked solutions and video solutions you can open after you answer. Start with the free diagnostic to see where you stand.

Lesson transcript

The narration of “Circuit Analysis in 4 minutes”, by chapter.

Introduction

Circuit analysis in four minutes. This is the toolkit the rest of power engineering borrows from. We will cover phasors, balanced three-phase circuits, the per unit system, symmetrical components, and complex power. Then work one short example and look at two traps.

What to expect

Expect 10 to 15 questions from this area and its reach is wider than that because protection, transmission, and machines all lean on it. You should be able to work with phasors in both forms, solve a balanced circuit per phase, build a per unit diagram, split an unbalanced set into sequences, and keep complex power straight. The goal is to set up any circuit quickly without losing a factor of root 3.

Phasors

Idea 1. Phasors turn calculus into algebra. At one frequency every voltage and current is a magnitude and an angle and inductors and capacitors become impedances. Kirchhoff's laws still hold only with complex numbers. 3 plus j4 is the same phasor as 5 at 53.1 degrees. Be fluent switching between the two forms on your calculator.

Three-phase

Idea 2. A balanced three-phase system reduces to one phase. The three-phase voltages are equal and 120 degrees apart. In a wye, the line voltage is root 3 times the phase voltage and leads it by 30 degrees in positive sequence. In a delta line current is root 3 times phase current. A balanced delta can be replaced by a wye of one-third the impedance.

Per unit

Idea 3. Per unit removes the transformers. Choose one MVA base for the whole system and a voltage base in each zone set by the transformer ratios. The base impedance in each zone is the base kV squared over the base MVA. Then every impedance sits on one diagram with no ideal transformers left in it.

Sequences

Idea 4. Symmetrical components untangle unbalance. Any three unbalanced phasors split into positive, negative, and zero sequence sets and each set sees its own network. The zero sequence voltage is one third of the sum of the three phases so it vanishes for a balanced set. Faults connect the sequence networks in patterns you learn to recognize.

Complex power

Idea 5. Complex power keeps the bookkeeping honest. S is P plus j Q and it equals the voltage times the conjugate of the current. The power triangle links real power, reactive power, and power factor and it is where every correction problem starts.

Mini-example

Now a mini example. A generator has a reactance of 0.15 per unit on its own rating of 50 MVA and 13.2 kV. The system base is 100 MVA and the generator zone has a base of 13.8 kV. Find the reactance on the system base. Multiply by the ratio of the bases. The MVA ratio is 100 over 50 or 2. The kV ratio, old over new squared, is 0.9149 so the new reactance is 0.15 times 2 times 0.9149 which is 0.274 per unit. Check it in ohms. 0.5227 ohms over the new base impedance of 1.9044 ohms gives the same 0.274 per unit.

Two traps

Trap 1. Forgetting to square the voltage ratio. Use 13.2 over 13.8 without the square and you get 0.287 per unit which is wrong. Impedance scales with voltage squared. Trap 2. Dropping the conjugate. Take 240 volts at 0 degrees and 10 amps lagging by 30 degrees. With the conjugate S is 2,078 plus j1,200, a lagging load absorbing VARs. Without it the reactive power flips sign and the load looks leading. Find out where you stand with the free diagnostic. Then practice this area with worked solutions at phasorprep.com