Three-phase power calculator
kW, kVA, kVAR, line current and power factor from the line voltage and any two of them.
Result
- Real power
- 100kW
- Apparent power
- 125kVA
- Reactive power, lagging
- 75kVAR
- Line current
- 150.4A
- Power factor, lagging
- 0.8
What it calculates
The power triangle of a balanced three-phase load. Give the line-to-line voltage and any two of real power, apparent power, reactive power, line current and power factor, and it fills in the rest. Apparent power comes from the line quantities; real power is its share set by the power factor; reactive power is what is left:
Lagging and leading
An inductive load such as a motor draws current that lags the voltage, and its reactive power is counted as positive. A capacitive load draws current that leads the voltage, and its reactive power is negative. Reactive power is entered as a size, and the lagging or leading choice sets its sign. Power factor alone cannot say which side the current is on, so the same number can describe either.
Worked example
A 480 V load takes 100 kW at a power factor of 0.8 lagging. Apparent power, reactive power and line current follow:
The current lags the voltage by 36.87 degrees, since the cosine of that angle is 0.8. Correcting the power factor toward 1 lowers the kVAR and the line current while the kW stays the same.
Assumptions
- The load is balanced and the voltages are sinusoidal.
- Voltage is line-to-line and current is the line current, so wye and delta loads are treated alike.
- Power factor is the displacement power factor. Harmonics are not included.
Questions
Why is there a √3 in the three-phase power formula?
Does this work for a delta-connected load?
Why can't I enter kVA and amps together?
Study areas that use this
For learning, not for design
Practice questions are on the way
Original PE Power questions, each with a verified worked solution. Join the waitlist to hear when the free diagnostic opens.
See the Founding Pass