Measurement and Instrumentation study guide
- Questions on the exam
- 6–9
- Practice questions published
- 8
Watch the lesson
What this area covers
Measurement and Instrumentation asks whether you can trust a number. It covers instrument transformers and the multipliers they bring, how accurate a metering or relaying chain is, the classic wattmeter connections for three-phase power, how the meter itself disturbs the circuit, and what different meters actually report when the waveform is not a clean sine. This area accounts for 6–9 questions on the exam. The arithmetic is light; the usual errors are in connections, ratios and definitions.
The ideas everything else rests on
Every secondary reading needs its multiplier. A meter on the secondary of a current transformer and a voltage transformer sees scaled-down quantities. Primary power is the meter reading times the CT ratio times the VT ratio. A current-only reading takes just the CT ratio, a voltage-only reading just the VT ratio. Write the ratios as fractions with units, such as 600 A to 5 A, so the direction of scaling is never in doubt.
Accuracy classes are promises over a range. A metering-class instrument transformer is accurate near rated current and burden, which is what revenue metering needs. A relaying-class CT trades that fine accuracy for the ability to reproduce many times rated current during a fault without saturating badly. Both depend on staying within the rated burden, so adding a long lead run or an extra device can quietly move a CT out of its class.
Two wattmeters measure three-wire power. In a three-wire system, two wattmeters measure total real power whatever the load balance or power factor: P = W1 + W2. For a balanced load, the difference between the readings also reveals the power factor angle. With the first meter on line a current and the a-to-b voltage, the second on line c current and the c-to-b voltage, and positive sequence,
At 0.5 power factor one meter reads zero, and below that one reads negative, which must be subtracted, not ignored. More generally, Blondel's theorem says a system with n wires needs n minus 1 measuring elements.
Meters load the circuit they measure. A voltmeter draws current through its internal resistance; across a high-resistance source, that current changes the very voltage being read. An ammeter adds series resistance. The size of the error comes from comparing the meter's resistance with the Thevenin resistance of the circuit at the measuring point.
Average-responding is not true RMS. Many simple meters rectify and average the waveform, then scale the result by the form factor of a sine wave. On a sine wave the answer is right. On a distorted current, such as the input of a rectifier or a variable-frequency drive, it can be badly off. A true-RMS meter computes the heating value directly and stays correct.
How to study it
- Work meter-multiplier problems for single-phase and three-phase installations, with CTs and VTs on both sides of a transformer.
- Check the primary values you find against the Three-phase power calculator, going from line voltage, current and power factor to kW, kVA and kVAR.
- Derive the two-wattmeter readings for balanced loads at several power factors, including below 0.5, and confirm that the sum always equals the total power. Check your readings and the power factor they give with the Two-wattmeter method calculator.
- Use the Symmetrical components calculator to see how an unbalanced set of currents breaks into sequences, which is what many protective and power-quality meters report.
- Finish with loading errors and waveform effects: a voltmeter across a divider, and the reading of an average-responding meter on a square wave and on a pulsed current.
Mistakes that cost points
- Inverting a ratio. Multiply secondary readings by the ratio to reach primary values. Dividing instead leaves the answer off by the square of the ratio.
- Dropping the sign of a negative wattmeter. Below 0.5 power factor one reading is negative, and the total is the algebraic sum.
- Applying the two-wattmeter power factor formula to an unbalanced load. The sum still gives total power; the angle formula only holds when the load is balanced.
- Trusting an average-responding meter on distorted waveforms. The sine-wave scaling no longer applies.
References worth having
- IEEE Std C57.13 (requirements for instrument transformers)
- ANSI C12.1 (code for electricity metering)
Try a free question
- Two-wattmeter methodMultiple choiceExam level
- 4–20 mA transducer scalingMultiple choiceWarm-up
- CT accuracy class and burdenMultiple choiceExam level
- Primary metering multiplierMultiple choiceWarm-up
Calculators for this area
Two-wattmeter method calculator
Total power, reactive power and power factor of a balanced three-wire load from its two wattmeter readings.
Open the calculatorThree-phase power calculator
kW, kVA, kVAR, line current and power factor from the line voltage and any two of them.
Open the calculatorSymmetrical components calculator
Phase phasors to zero, positive and negative sequence components and back, drawn as phasors.
Open the calculator
Practice every Measurement and Instrumentation question
The full set comes with worked solutions and video solutions you can open after you answer. Start with the free diagnostic to see where you stand.
Lesson transcript
The narration of “Measurement and Instrumentation in 4 minutes”, by chapter.
Introduction
Measurement and Instrumentation in four minutes. This area asks whether you can trust a number. We will go through meter multipliers, accuracy classes, the two-wattmeter method, how a meter loads the circuit, and true RMS. Then work one short example and look at two traps.
What to expect
Expect six to nine questions from this area. The arithmetic is light. The usual errors are in connections, ratios, and definitions. You should be able to scale secondary readings to primary values, pick an accuracy class, use two wattmeters, estimate a loading error, and say what a meter reports on a distorted wave.
Meter multipliers
Idea one, every secondary reading needs its multiplier. A meter behind a current transformer and a voltage transformer sees scaled-down quantities. Primary power is the meter reading times the CT ratio times the VT ratio. A current reading takes only the CT ratio and a voltage reading only the VT ratio. Write each ratio with its units like 200 amps to 5 amps so the direction is never in doubt.
Accuracy classes
Idea two, accuracy classes are promises over a range. A metering class transformer is accurate near rated current and burden which revenue metering needs. A relaying class CT gives up that fine accuracy so it can reproduce many times rated current during a fault without saturating badly. Both depend on staying inside the rated burden so a long lead run can quietly push a CT out of its class.
Two wattmeters
Idea three, two wattmeters measure three-wire power. The first meter takes line a current and the a to b voltage. The second takes line c current and the c to b voltage. Their sum is the total real power whatever the balance or power factor. For a balanced load the difference also gives the power factor angle.
Meter loading
Idea four, meters load the circuit they measure. A voltmeter draws current and across a high resistance source that changes the very voltage being read. An ammeter adds series resistance. Compare the meter's resistance with the Thévenin resistance at the measuring point to size the error.
True RMS
Idea five, average responding is not true RMS. A simple meter rectifies and averages the wave then scales it by the form factor of a sine. On a sine wave that is right. On the distorted current of a rectifier or a drive it can be badly off. A true RMS meter computes the heating value directly.
Mini-example
Now a mini-example, a balanced three-wire load is metered with two wattmeters through CTs rated 200 amps to 5 amps and VTs rated 4,200 volts to 120 volts. The meters read 300 watts and 500 watts. Find the primary power and the power factor. The CT ratio is 40 and the VT ratio is 35 so the multiplier is 1,400. The secondary total is 800 watts so the primary power is 800 times 1,400 which is 1.12 megawatts. For the angle tangent theta is 1.732 times the difference 200 over the sum 800: 0.433. Theta is 23.4 degrees and the power factor is 0.918. Every step used only the two readings and the two ratios.
Two traps
Trap one, inverting a ratio. Divide 800 watts by 1,400 and you get 0.57 watts off by the square of the ratio. Secondary readings are multiplied up to primary values never divided. Trap two, dropping the sign of a negative wattmeter. Below 0.5 power factor one meter reads negative. Suppose the readings are minus 100 watts and 500 watts. The total is 400 watts not 600. Add the readings with their signs every time. Find out where you stand with the free diagnostic then practice this area with worked solutions at phasorprep.com