Two-wattmeter method calculator
Total power, reactive power and power factor of a balanced three-wire load from its two wattmeter readings.
Result
- Power factor
- 0.866
- Total power, P
- 60kW
- Reactive power, |Q|
- 34.64kVAR
- Apparent power, S
- 69.28kVA
- Power-factor angle, |φ|
- 30°
Balanced three-wire load. The readings alone do not say whether the power factor is lagging or leading: that depends on the phase sequence.
What it calculates
The total power, reactive power and power factor of a balanced three-phase, three-wire load measured with two wattmeters. Each meter has its current coil in one line and its potential coil from that line to the third line, the one with no current coil. For a balanced load with power-factor angle φ, the two meters read:
Their sum is the total power, and their difference, times √3, is the reactive power. The ratio of the two gives the power-factor angle without knowing the voltage or the current:
Worked example
The meters read 40 kW and 20 kW. The calculator opens on this case:
When one meter reads negative
Below a power factor of 0.5 the angle in the lower meter's reading passes 90°, so that meter reads negative. Keep the sign. With readings of 50 kW and −10 kW:
At exactly 0.5 power factor (φ = 60°) the lower meter reads zero. At unity power factor the two readings are equal.
Readings from a known load
To go the other way, from a load to the readings you should see, open the helper under the inputs. It finds the line current from the total power, the line voltage and the power factor:
and puts it into the two reading formulas above. For a 50 kW load at 480 V and 0.80 power factor, the line current is 75.18 A and the meters read 35.83 kW and 14.17 kW, which add back to 50 kW. To get line current from other combinations of kW, kVA and power factor, see the three-phase power calculator.
Assumptions
- The load and the supply are balanced. The sum of the readings is the total power of any three-wire load, but the reactive power and power factor formulas hold only for a balanced one.
- The circuit is three-wire. A four-wire load with current in the neutral needs three wattmeters, one per phase.
- The meters are ideal: no burden on the circuit and no ratio or phase-angle error from instrument transformers.
- The result gives the size of the angle and of the reactive power. Whether the load is lagging or leading depends on the phase sequence and on which meter reads higher, which the two numbers alone do not show.
Questions
Why does one wattmeter read negative?
Can the readings tell me whether the power factor is lagging or leading?
Does the two-wattmeter method work for an unbalanced load?
Free practice problems that use this
Study areas that use this
For learning, not for design
Put the methods to work
Original PE Power practice questions, each with a worked solution and an answer recomputed by a script. Find your weak areas with the free diagnostic, or try a sample question first.