Motor-starting voltage dip calculator
Bus voltage while a motor starts across the line, from the source, the transformer and the motor's locked-rotor kVA.
Result
- Bus voltage, percent of nominal
- 92.92%
- Voltage dip
- 7.08%
Bus voltage on a 0 to 100% scale. Ticks mark 85% (above the bar) and 90% (below it) of nominal.
- Zs (source)
- 0.006pu
- Zt (transformer)
- 0.0575pu
- Zm (motor, locked)
- 0.8333pu
Per unit on the transformer kVA, with the bus at 1.0 pu before the start and no other load.
What it calculates
The bus voltage at the moment an induction motor is started across the line, and how far it falls below nominal. At standstill the motor draws locked-rotor current, so it looks like a small fixed impedance connected to the bus. That impedance, the transformer and the utility source form a voltage divider. All three are put on the transformer kVA as the base:
The motor's share of the divider is the bus voltage, and the dip is what is left over:
Locked-rotor kVA from current
Enter the motor's locked-rotor kVA directly, or open the helper and enter the locked-rotor current and the line-to-line voltage it was measured or quoted at:
Worked example
A 1,500 kVA transformer with 5.75% impedance feeds a motor whose locked-rotor draw is 1,800 kVA. With an infinite source (no utility impedance):
Now add a utility source with 250 MVA of available short-circuit power. The calculator opens on this case. The source adds 0.006 pu in series, so the bus sags further:
Compared with the shortcut
A common shortcut multiplies the transformer %Z by the ratio of locked-rotor kVA to transformer kVA. For the infinite-source case above, that gives 5.75% × 1,800 / 1,500 = 6.9%, while the divider gives 6.45%. The shortcut leaves the motor's own impedance out of the denominator, as if the motor still drew its full locked-rotor current at nominal voltage. In fact the motor's current falls as the bus voltage falls, so the shortcut overstates the dip. It also has no place for the utility source impedance.
Assumptions
- The impedances are added as magnitudes, as if they all had the same angle. In practice the source and transformer are mostly reactive and the motor at locked rotor has a lower power factor, so the true dip is somewhat smaller than this adds up to.
- There is no other load on the bus before the start, and the bus is at 1.0 pu before it.
- The motor is a constant impedance at its locked-rotor value for the whole calculation. It does not model the motor speeding up, so it gives the dip at the first instant of the start, which is the worst case for an across-the-line start.
- The transformer is the only series impedance between the source and the motor, and its taps are at nominal. Cable impedance between the transformer and the motor is not included. To add it, see the voltage drop calculator.
- Locked-rotor kVA is taken from the manufacturer's data. This tool does not estimate it from a code letter.
Questions
How large a voltage dip is acceptable when a motor starts?
Where do I find the locked-rotor kVA?
Why is this result slightly different from the %Z × LR kVA / kVA shortcut?
Study areas that use this
For learning, not for design
Practice questions are on the way
Original PE Power questions, each with a verified worked solution. Join the waitlist to hear when the free diagnostic opens.
See the Founding Pass