Electric Power Devices study guide
- Questions on the exam
- 8–12
- Practice questions published
- 11
Watch the lesson
What this area covers
Electric Power Devices centres on the transformer, with a growing share for the equipment that now sits beside it: battery energy storage, photovoltaic plants and wind turbines. You need to model a transformer from its test data and nameplate, predict how it behaves under load and in parallel, and read the ratings of inverter-connected sources well enough to size and compare them. This area accounts for 8–12 questions on the exam.
The ideas everything else rests on
The equivalent circuit comes from two tests. A transformer is modelled as an ideal transformer plus a series branch (winding resistance and leakage reactance) and a shunt branch (core loss and magnetising reactance). The open-circuit test, at rated voltage with one winding open, gives the shunt branch. The short-circuit test, at reduced voltage with one winding shorted and rated current flowing, gives the series branch. Know which side each test is usually run on and refer values to one side before you combine them.
Percent impedance is a short-circuit test result in disguise. It is the share of rated voltage that drives rated current through a shorted transformer. It sets fault current, voltage regulation and how parallel units share load. On the transformer's own base, percent impedance divided by 100 is the per-unit impedance, ready to drop into a system diagram after a change of base. Parallel units first need the same voltage ratio, phase shift and polarity, or circulating current flows even with no load. Once those match, load divides in inverse proportion to impedance on a common base, so the unit with the lower percent impedance on its own rating reaches full load first.
An autotransformer carries most of its power by conduction. Only the part of the power that crosses the series winding is transformed magnetically. That is why an autotransformer of a given winding rating can pass much more power when the two voltages are close:
The trade-off is no electrical isolation and a lower impedance, which raises fault current.
Efficiency peaks where the losses match. Core loss is roughly constant whenever the unit is energised; copper loss grows with the square of load. Efficiency is
and it is highest at the load where copper loss equals core loss. All-day efficiency uses energy over 24 hours instead of power at one instant, which rewards low core loss for lightly loaded distribution units.
Storage and PV have two ratings each. A battery system has a power rating and an energy rating; their ratio is its duration, and round-trip losses mean you get back less than you put in. A PV plant has a DC array rating at standard test conditions and an AC inverter rating; when the array is larger than the inverter, output clips at the inverter limit on bright days.
How to study it
- Reduce open-circuit and short-circuit test data to an equivalent circuit, referred first to the high side and then to the low side.
- Compute full-load current on both sides, and fault current from percent impedance, with the Transformer current calculator.
- Move a nameplate impedance onto a system base with the Per-unit converter, then work load sharing between two parallel units with unequal impedances.
- Work regulation and efficiency at several load levels and power factors; find the load for peak efficiency and compute an all-day figure from a simple load profile.
- Practise three-phase bank connections (wye–wye, delta–wye, delta–delta) and their phase shifts, and check kVA and current with the Three-phase power calculator.
- Finish with storage and PV ratings: duration, usable energy and inverter loading.
Mistakes that cost points
- Leaving values on the wrong side. Impedances from the two tests may be measured on different windings. Refer both to one side with the square of the turns ratio before adding them.
- Sharing load by kVA rating instead of impedance. Equal ratings do not mean equal shares if the per-unit impedances differ.
- Using the winding rating as the throughput of an autotransformer. The power it passes is larger than its winding rating; know which one the problem gives you.
- Scaling core loss with load. Only copper loss changes with the square of load. Core loss stays put as long as voltage does.
References worth having
- IEEE Std C57.12.00 (general requirements for liquid-immersed transformers)
- IEEE Std 1547 (interconnection of distributed energy resources)
- Chapman, Electric Machinery Fundamentals: the transformer chapter
Try a free question
- Transformer all-day efficiencyMultiple choiceExam level
- Parallel transformer loadingMultiple choiceExam level
- Transformer voltage regulationMultiple choiceWarm-up
Calculators for this area
Transformer current calculator
Primary and secondary full-load current, and the largest secondary fault current its impedance allows.
Open the calculatorPer-unit converter
Base current and impedance, and an impedance moved from one MVA and kV base to another.
Open the calculatorThree-phase power calculator
kW, kVA, kVAR, line current and power factor from the line voltage and any two of them.
Open the calculator
Practice every Electric Power Devices question
The full set comes with worked solutions and video solutions you can open after you answer. Start with the free diagnostic to see where you stand.
Lesson transcript
The narration of “Electric Power Devices in 4 minutes”, by chapter.
Introduction
Electric power devices in four minutes. This area is built around the transformer with a growing share for the equipment beside it, battery storage, solar plants, and wind turbines. We will cover the equivalent circuit, percent impedance, the autotransformer, efficiency, and storage and solar ratings. Then work one example and look at two traps.
What to expect
Expect 8 to 12 questions from this area. You should be able to build a transformer model from test data and the nameplate, predict how it behaves under load and in parallel, find its efficiency, and read storage and solar ratings well enough to size and compare them.
Equivalent circuit
Idea one, the equivalent circuit comes from two tests. The model is an ideal transformer plus a series branch, the winding resistance and leakage reactance, and a shunt branch, the core loss and magnetizing reactance. The short-circuit test at reduced voltage with rated current flowing gives the series branch. The open circuit test at rated voltage gives the shunt branch. Refer both to one side before you combine them.
Percent impedance
Idea two, percent impedance is a short-circuit test result in disguise. It is the share of rated voltage that pushes rated current through the shorted transformer. Divide by 100 and you have the per unit impedance on the transformer's own base. It sets fault current, regulation, and load sharing. Parallel units need the same ratio, phase shift, and polarity, and then they share load in inverse proportion to their impedance.
Autotransformer
Idea three, an autotransformer carries most of its power by conduction. Only the part that crosses the series winding is transformed magnetically, so a given winding rating passes much more power when the two voltages are close. The price is no isolation and a lower impedance, which means more fault current.
Efficiency
Idea four, efficiency peaks where the losses match. Core loss stays almost constant whenever the unit is energized. Copper loss grows with the square of the load. Efficiency is highest at the load where the two are equal. All-day efficiency uses energy over 24 hours, which rewards low core loss in lightly loaded units.
Storage and solar
Idea five, storage and solar each have two ratings. A battery has a power rating and an energy rating, and their ratio is its duration. A solar plant has a DC array rating and an AC inverter rating. When the array is larger than the inverter, output clips flat at the inverter limit on bright days.
Mini-example
Now a mini-example. A 500 kVA transformer has 1.2 kilowatts of core loss and 4.8 kilowatts of copper loss at full load. At what load is its efficiency highest and what is that efficiency at unity power factor? Copper loss scales with the square of the load fraction, so set it equal to the core loss. The fraction is the square root of 1.2 over 4.8, which is 0.5. Peak efficiency comes at half load, 250 kVA. There the copper loss is also 1.2 kilowatts, so the losses total 2.4. The efficiency is 250 over 252.4, or 99.05%. That is the top of the curve.
Two traps
Trap one, scaling core loss with load. Halve the core loss at half load and the losses drop to 1.8 kilowatts, giving 99.29%, which is too high. Core loss stays put as long as the voltage does. Trap two, sharing load by rating instead of impedance. Two units of 1,000 kVA each, in parallel, at 5 and 6.25%, carry 1,800 kVA. Split evenly, each looks safe at 900, but load divides inversely with impedance, so the 5% unit takes 1,000 kVA, a full load, and the other takes 800. Find out where you stand with the free diagnostic, then practice this area with worked solutions at phasorprep.com.